Copper is of uniform Resistance.
Red, Black, Blue, Yellow, Green (for Earthing)
Coils are available in the length of 90 meters.
Single core, unsheathed wired in voltage grade 1100v.
Available in 6 sq. mm and 10 sq. mm on request.
Available in 2 Core and 3 Core on order.
Nominal Cross Section Area of conductor Sq. Mm | Number/Nom. Dia of wires* (Nom.)Number/mm | Thickness of Insulation(Nom.)mm | Appros. Overall diameter mm | Current Carryin Capacity 2 Cables Single Phase | Resistance(max) O.C at 20 Ohm/km | |
---|---|---|---|---|---|---|
Concuit/Trunking | Unenclosed clipped directly to a surface or oncable trays | |||||
0.75 | 24/0.02** | 0.6 | 2.6 | 8 | 9 | 26.0 |
1 | 14/0.30** | 0.7 | 2.8 | 12 | 14 | 18.1 |
1.5 | 22/0.30** | 0.8 | 3 | 16 | 18 | 12.1 |
2.5 | 36/0.30** | 0.8 | 3.8 | 20 | 24 | 7.41 |
4 | 56/0.30** | 0.8 | 4.5 | 24 | 32 | 4.95 |
Test | Fuction | Specification/Test Method | Specific Values Normal PVC Type A |
FR PVC Type C1 |
---|---|---|---|---|
Critical Oxygen Index | To determine the % oxygen required for supporting combustion of insulating material at Room Temperature | IS 10810 P -58 | 23% | >23% |
Temperature Index | To determine at what Temperature normal oxygen content of 21% in air will support combustion of insulating material | IS 10810 P -64 | 150 C | >150C |
Acid Gas Generation | To ascertain the amount of Hydrochloric acid gas evolved from insulation of wire under FIRE | IS 10810 P -59 | <45-50% | <45-50% |
Light Transmission(smoke density) | To Determine the visibility(Light Transmission) when insulating material is on FIRE | ASTM -D 2843 | <20 % | <20% |
Note: DARIL LIGHTING PVT LTD will not be liable for damages arising due to incorrect installations. The above data is indicative and may be revised without prior intimation.